EMS DT1Next

DT1Next is an energy management system (EMS) for connection points with solar and batteries. It runs on its own control unit in the site switchboard, meets grid commitments and uses the remaining capacity for savings and revenue. Since 2020 our first-generation DT1 system has been controlling dozens of sites, 16 of them connected to medium voltage.

Discuss DT1Next for your site References in 3D

Runs on
control unit in the site switchboard, independent of internet
Metering
at the grid connection within milliseconds, per phase
Evaluation
per quarter hour, like the billing meter
Interfaces
grid operator RTU, aFRR aggregator, onlineWatt portal

Fixed order of commitments

Each service only narrows the range allowed by the services above it. For every device the deciding service and reason are logged.

  • device protection: BMS limits, devices offline, invalid metering
  • grid operator dispatch via RTU with absolute priority
  • reserved capacity: never exceeded in normal operation
  • aFRR balancing for registered devices
  • commercial flexibility activations
  • site services according to the economic plan

Working with RTU and dispatch

Grid operator commands take precedence over all other command sources, for the whole site.

  • active power steps for export and import, reactive power steps
  • our own RTU, or any other manufacturer’s RTU via our Modbus RTU table
  • relay-only RTUs connect to the control unit inputs
  • actual device values reported to the RTU
  • Q = 0 at export above 20 % of installed capacity (EG.D requirement)
  • time-limited service mode for dispatch tests, always logged

Reactive power and power factor

When batteries and solar cover most active demand, reactive demand remains and the power factor drops. DT1Next controls inverter reactive power continuously.

  • target: slightly inductive at the grid connection, never capacitive
  • quarter-hour reactive energy account per quadrant
  • split between inverters by free apparent power; active power always first
  • works with existing compensation, or blocks it via a contact
  • avoided surcharges reported in money

Balancing services and flexibility

Through an aggregator the battery can provide automatic frequency restoration reserve (aFRR) while still protecting the site from peaks.

  • aggregator writes the setpoint via Modbus TCP, applied within seconds
  • upper and lower parts of capacity reserved for aFRR
  • available power reported already limited by reserved capacity
  • state of charge restored to the reserved band after activation
  • aggregator link supervision with safe fallback
  • commercial flexibility without draining the peak reserve

Energy sharing

Surplus solar and battery energy can be shared within an energy community or between sites of one company.

  • export limited to what the community consumes
  • connection to the community portal
  • sharing economics in the plan together with spot prices
  • on one device sharing and aFRR are currently exclusive; configuration decides

Load control via contacts

Loads are another source of flexibility: electric water heaters, heat pumps, HVAC, cooling and pumps.

  • 16 relay outputs, 6 analogue 0–10 V outputs and 2 PWM outputs on the control unit
  • switching and continuous control: SG ready, power controllers, drives
  • load shedding by priority when the battery cannot cover a peak
  • use of solar surplus and cheap or negative prices
  • daily need with deadline in the cheapest quarter hours
  • appliance protection: minimum run and rest times, temperature limits
  • beacon for operators: limit at risk, surplus, cheap energy

Quarter hours and reserved capacity

DT1Next tracks reserved capacity and the monthly quarter-hour maximum continuously.

  • import and export per phase, like billing metering
  • forecast to the end of each quarter hour
  • peak reserve learned from operation
  • early warning when demand exceeds what was learned
  • safety disconnection by contactor, verified at the grid meter
  • thermal protection of cables and joints with Pt1000 sensors

Prices, plan and economics

DT1Next knows quarter-hour prices, learns site consumption and plans the battery for the next day.

  • plan after day-ahead prices are published, continuously updated
  • arbitrage, charging at negative prices, export limiting at low prices
  • external plan from an optimiser via API
  • per quarter hour: paid, earned and saved compared with no technology

DT1Next feature checklist

What DT1Next controls and watches. Useful for comparing offers and for technical specifications.

Grid commitments

  • Dispatch control via RTU
  • Third-party RTU via Modbus RTU table
  • RTU reactive power steps and Q = 0 at export above 20 %
  • Continuous reactive power and power factor control
  • Reserved export capacity never exceeded
  • Reserved import capacity never exceeded
  • Quarter-hour average tracking
  • Per-phase metering and quarter-hour account
  • Safety disconnection verified at the grid meter
  • Thermal disconnection on overheating joints
  • Commitments hold without internet

Flexibility and markets

  • aFRR via aggregator
  • Commercial flexibility activations
  • Spot buy, sell, arbitrage
  • Export limiting at low or negative prices
  • Day-ahead plan
  • External plan via API
  • Energy community sharing

Site services

  • Self consumption, optionally per phase
  • Peak shaving
  • Automatic learned peak reserve
  • Early warning before the reserve runs out
  • Time windows and manual charging plan
  • Reserve recharge from the grid
  • Battery capacity bands between services
  • Power split and state-of-charge balancing

Devices and wiring

  • Several batteries from different makers
  • Several solar plants, including meter-only legacy plants
  • Multiple meters, two transformers, sub-metering
  • Controlled loads: relay, SG ready, 0–10 V, PWM
  • Temperature sensors
  • EV chargers
  • Ripple control and billing meter cross-check

Operation and data

  • onlineWatt portal: data, events, alarms
  • Economics in money per quarter hour
  • Decision history: which service and why
  • Remote management and updates
  • Economic study on site data before deployment

DT1Next FAQ

What is DT1Next?

An energy management system (EMS) for businesses and sites with solar and batteries, running on a control unit on site.

Does DT1Next work without internet?

Yes. Dispatch control, reserved capacity and protection hold without internet. The cloud only supplies prices, forecasts and plans.

Can a battery provide aFRR and peak shaving at the same time?

Yes. Capacity is split into bands, and aFRR never exceeds the reserved capacity.

Does DT1Next work with third-party RTUs?

Yes, via our Modbus RTU table or the control unit inputs for relay-step RTUs.

How does DT1Next help with power factor?

It controls inverter reactive power so the site stays slightly inductive, reducing power factor surcharges.

Can it control a water heater or heat pump?

Yes, through the control unit relay and analogue outputs.